Yearly kWh Savings
Yearly Energy Cost Savings
Chemical cleaning of evaporators across AHU 1–13. Projected savings: 34,597 kWh/year and $4,152/year.
View Details
Repair faulty humidifier control and reduce discharge air humidity setpoints on AHU 1 and AHU 4. Projected savings: 33,925 kWh/year and $4,071/year
View Details
Troubleshoot/repair or replace the VFD on AHU 1 and return it to normal modulation based on static pressure and CFM demand. This was the single biggest savings measure: 129,118 kWh/year and $15,494/year.
View Details
Implement BAS programming and optimize static pressure setpoints on AHU 1 and AHU 4. Projected savings: 19,059 kWh/year and $2,287/year.
View Details
Reduce chilled water differential pressure setpoint to 9.7 psi for P-12 and P-13. Projected savings: 17,007 kWh/year and $2,041/year.
View Details
We service commercial and industrial properties in all 50 states.