No Cost Building Tune-Up Saves MD Office Building $28,045 Per Year
How we achieved these savings
TES identified 5 energy conservation measures:
Repair VFD and remove from By-pass mode
Yearly Savings: |
$15,494.18 |
Yearly Electric Savings: |
129,118.15 kWh |
Tune Up HVAC Units
Yearly Savings: |
$4,151.60 |
Yearly Electric Savings: |
34,597 kWh |
Repair Humidity Control and Optimize Setpoints
Yearly Savings: |
$4,070.98 |
Yearly Electric Savings: |
33,924.82 kWh |
Implement AHU Duct Static Reset
Yearly Savings: |
$2,287.13 |
Yearly Electric Savings: |
19,059.41 kWh |
Optimize Pump Differential Pressure Setpoint
Yearly Savings: |
$2,040.86 |
Yearly Electric Savings: |
17,007.17 kWh |
Customer Cost: $0
Total Yearly Savings: $28,045
Total Yearly Energy Savings: 233,706 kWh