No Cost Building Tune-Up Saves MD Office Building $28,045 Per Year

How we achieved these savings
  • TES engineers performed an ASHRAE level II energy audit to find inefficiencies in the buildings HVAC, mechanical and control systems.

TES identified 5 energy conservation measures:
Repair VFD and remove from By-pass mode
Yearly Savings: $15,494.18
Yearly Electric Savings: 129,118.15 kWh
Tune Up HVAC Units
Yearly Savings: $4,151.60
Yearly Electric Savings: 34,597 kWh
Repair Humidity Control and Optimize Setpoints
Yearly Savings: $4,070.98
Yearly Electric Savings: 33,924.82 kWh
Implement AHU Duct Static Reset
Yearly Savings: $2,287.13
Yearly Electric Savings: 19,059.41 kWh
Optimize Pump Differential Pressure Setpoint
Yearly Savings: $2,040.86
Yearly Electric Savings: 17,007.17 kWh

Customer Cost: $0

Total Yearly Savings: $28,045

Total Yearly Energy Savings: 233,706 kWh